Functional Descriptions (By Parameter No.) |
LOCAL/EXTERNAL FREQUENCY (Parameter No. 09) |
Used to select whether the frequency signal is to be set from the operation panel (local) or with an input signal (external).
Data setting value | Mode display | Local / External | Frequency setting signal details | Applicable control circuit terminal No. |
0 | L | Local | Set frequency from operation panel | ----------------------- |
1 2 3 4
|
E | External | Potentiometer signal 0-5(V) voltage signal 0-10(V) voltage signal 4-20(mA) current signal |
Terminal Nos. 1,2 and 3 (Connect wiper of potentiometer to terminal 2) Terminal Nos.2 and 3 (2:+,3:-) Terminal Nos.2 and 3 (2:+,3:-) Terminal Nos.4 and 3 (4:+,3:-) |
Note) If an analog signal is input from an external source when the data setting is 1 to 4, the inverter output will start and stop at a boundary of approx. 1/100 of the input signal's fill scale. (Zero volt stop function)