LOCAL/EXTERNAL CONTROL (Parameter No. 08) |
Used to select whether to operate the inverter with the operation panel push buttons (local) or with input signals (external).
Data setting value | Mode display | Local/External | Panel reset function | Signal format and button operation | Control terminal connection diagrams |
0 | L | Local | Provided | -------------- | |
1 4 |
E | External | Not provided Provided |
2-wire signal Start/Stop and Forward/Reverse 3-wire signal Start, Forward/ reverse and Stop |
|
2 5 |
E | External | Not provided Provided |
2-wire signal Forward start/stop Reverse start/stop |
|
3 6 |
E | External | Not provided Provided |
3-wire signal Forward start Reverse start Stop |