Functional Descriptions (By Parameter No.)

LOCAL/EXTERNAL CONTROL (Parameter No. 08)

Used to select whether to operate the inverter with the operation panel push buttons (local) or with input signals (external).

Data setting value Mode display Local/External Panel reset function Signal format and button operation Control terminal connection diagrams
0 L Local Provided --------------
1

4

E External Not provided

Provided

2-wire signal Start/Stop and Forward/Reverse

3-wire signal Start, Forward/ reverse and Stop

2

5

E External Not provided

Provided

2-wire signal

Forward start/stop Reverse start/stop

3

6

E External Not provided

Provided

3-wire signal

Forward start Reverse start

Stop

When a fault trip occurs, the state cannot be reset with the external stop signal. Instead use the stop SW signal on the operation panel to reset. Note that if the reset lock out function is used, that function will have the priority. Resetting with the terminals is also valid.