Functional Descriptions (By Parameter No.) |
VOLTAGE COMPENSATION CONSTANT and SLIP COMPENSATION FREQUENCY Setting (Parameter No. 69 & 70) |
Used to set the motor constants required for vector control with data values.
(Voltage compensation constant setting : parameter No. 69)
Data setting range (V) | 0.01 to 99.99 (can be set in 0.01 units) |
Calculate the constants with the following method, and set the results as the data.
R : Resistance value of one phase including wiring impedance. (1/2 of resistance value measured between motor terminals) I : (equivalent current) Inverter rated current equivalent to motor capacity
Equivalent current (A) | Equivalent current (A) |
Motor capacity (kW) | 20V type | 400V type | Motor capacity (kW) | 200V type | 400V type | |
0.2 | 2.3 | -------- | 1.5 | 8 | 4.0 | |
0.4 | 3 | -------- | 2.2 | 11 | 6.0 | |
0.75 | 5 | 2.1 | 3.7 | 17.5 | 9.4 |
If the set value is too large : an overcurrent trip may occur.
Data setting range (Hz) | - 5.00 to + 5.00 (can be set in 0.01 units) |
NO No. of motor poles
N1 : Motor rated speed (at 60Hz)
Note) If the set value is not adequate :