Functional Descriptions (By Parameter No.)

VOLTAGE COMPENSATION CONSTANT and SLIP COMPENSATION FREQUENCY Setting (Parameter No. 69 & 70)

Used to set the motor constants required for vector control with data values.

(Voltage compensation constant setting : parameter No. 69)

Data setting range (V) 0.01 to 99.99 (can be set in 0.01 units)

Calculate the constants with the following method, and set the results as the data.

R : Resistance value of one phase including wiring impedance. (1/2 of resistance value measured between motor terminals) I : (equivalent current) Inverter rated current equivalent to motor capacity

Equivalent current (A) Equivalent current (A)

Motor capacity (kW) 20V type 400V type Motor capacity (kW) 200V type 400V type
0.2 2.3 -------- 1.5 8 4.0
0.4 3 -------- 2.2 11 6.0
0.75 5 2.1 3.7 17.5 9.4

If the set value is too large : an overcurrent trip may occur.

Data setting range (Hz) - 5.00 to + 5.00 (can be set in 0.01 units)

NO No. of motor poles

N1 : Motor rated speed (at 60Hz)

Note) If the set value is not adequate :