Electromotors

Dublin - Ireland

Tel : 353 - 1 - 830 9155

Fax : 353 - 1 - 830 9270

Functional Descriptions (By Parameter No.)

MAX OUTPUT VOLTAGE (Parameter No. 62)

Used to set the max. output voltage.

Data setting range (V) 0 . 1 ~ 500 (can be set in 1 units)

* When "0" is set, the power supply voltage value will be output.

Notes)

1. A voltage exceeding the power supply voltage cannot be output.

2. This setting does not affect the DC braking level.

3. This setting is used only for the V/F control (when parameter No. 56 is set to "0")

(This setting is not used for vector control (when parameter No. 65 is set to "1").

Return to Homepage Return to KCL Help Go to Explanation Parameter No.62