MONITOR SELECT and LINE SPEED MULTIPLIER (Parameter Nos. 60 & 61)

Used to select the details of the operation panel's main display and voltage output signal (control circuit terminal No. 5).

(Parameter No. 60 : Monitor details selection)

Data setting value Dispaly and details of voltage output (according to target) Operation panel main display value
0 Command frequency Frequency
1 Output frequency Frequency
2 Command frequency Line speed (speed)
3 Output frequency Line speed (speed)

The output frequency and command frequency are the same. Note) The motor is controlled at a speed that meets the command frequency, so the command frequency and output frequency may not match.

Used to set the multiplier in regard to the frequency when the line speed is displayed on the main display of the operation panel.

Data setting range 0.1 ~ 100 (can be set in 0.1 units)

(Example 1) When displaying the line speed