Functional Descriptions (By Parameter No.) |
MONITOR SELECT and LINE SPEED MULTIPLIER (Parameter Nos. 60 & 61) |
Used to select the details of the operation panel's main display and voltage output signal (control circuit terminal No. 5).
(Parameter No. 60 : Monitor details selection)
Data setting value |
Dispaly and details of voltage output (according to target) |
Operation panel main display value |
0 |
Command frequency |
Frequency |
1 |
Output frequency |
Frequency |
2 |
Command frequency |
Line speed (speed) |
3 |
Output frequency |
Line speed (speed) |
- Output frequency and command frequency
- Output frequency : Frequency currently being output by the inverter
- Command frequency : Frequency to be controlled by the inverter in regard to the frequency setting signal while taking the acceleration/deceleration time, etc., into consideration (calculating).
- * For V/F control (parameter No. 65 is set to "0")
The output frequency and command frequency are the same.
- * For vector control (parameter No. 65 is set to "1")
Note) The motor is controlled at a speed that meets the command frequency, so the command frequency and output frequency may not match.
(Parameter No. 61 : LINE SPEED MULTIPLIER setting)
Used to set the multiplier in regard to the frequency when the line speed is displayed on the main display of the operation panel.
Data setting range |
0.1 ~ 100 (can be set in 0.1 units) |
(Example 1) When displaying the line speed
Line speed (m/min) = f (Hz) x K sets the multiplier
Set 0.5 when the line speed is 30m/min at f=60Hz
(Example 2) When displaying the speed :
Speed 9rpm) - f (Hz) x 120
(No. of Poles) (Set 30 for a 4-pole motor)
1. A line speed exceeding "10000" cannot be displayed.
2. If the line speed multiplier is set to "100", set the data and then turn the power off. Turn the power on again after waiting at least one minute.