0-5V OUTPUT VOLTAGE COMPENSATION (Parameter No. 59)

The voltage signal that is proportional to the "command frequency" or "output frequency" output from control circuit terminal No. 5 is output linearly from the stop O(V) to the 5V MAX. FREQUENCY setting value (parameter No. 15) when it is the default value.

The 5V value for the above MAX. FREQUENCY setting value (parameter No. 15) can be adjusted with this mode.

Data setting range (%) (Adjustment range) 75 to 125 (can be set in 1% units)

Notes)

1. Set whether the voltage signal is proportional to the "command frequency" or to the "output frequency" with parameter No. 60. (See parameter No. 60 for details)

2. Voltage signal output during vector control (when parameter No. 15 is set to "1")

During vector control, the inverter controls the motor with a speed that matches the "command frequency". Thus, a frequency higher than the "command frequency" may be output.

(When voltage signal output details are "command frequency")

(When voltage signal output details are "output frequency")