Functional Descriptions (By Parameter No.) |
LOWER and UPPER FREQUENCY CLAMP (Parameter Nos. 54 & 55) |
Used to set the lower and upper limits of the output frequency
(Parameter No. 54 : LOWER FREQUENCY CLAMP setting)
(Parameter No. 55 : UPPER FREQUENCY CLAMP setting)
Data setting range (Hz) | 0.2 ~ 400 (0.2 ~ 100Hz : 0.01 units / 100 ~ 400Hz: 0.1 untis) |
Notes)
1. If the upper frequency clamp is lower than the maximum output frequency (parameter No. 15), the upper frequency clamp will have the priority.
2. If the lower frequency clamp is higher than the upper frequency clamp (reverse operation setting), the upper frequency clamp will have the priority.