RIDE-THROUGH RESTART (Parameter No. 51)
Data setting value Min. 15msec ot less (Note 1) Min. 15 msec is exceeded (Note 1) Min. 100msec or less (Note 2) Min. 100msec is exceeded (Note 2)

0 Operation continues
    LU trip occurs, and the operation takes place according to the details set in the start mode.
    "LU" is saved in the fault memory.
1 Operation continues
    Restarts from Ohz after the wait time has elapsed.
    "LU" is saved in the fault memory.
    Operation takes place according to the details set in the start mode.
2 Operation continues
    motor speed is detected after the wait time has elapsed, and the inverter restarts at a frequency corresponding to the speed.
    "LU" is saved in the fault memory.
    "LU" is saved in the fault memory.