Functional Descriptions (By Parameter No.) |
POWER LOSS START MODE (Parameter No. 50) |
|
Outline operation | Details of operation |
0 | Run | Operation starts immediately when the power is turned ON and the low voltage level (LU Level) is exceeded. |
1 | "OP" stop | The inverter OP trips when the power is turned ON and the low voltage level (UL level) is exceeded. Turn the run signal ODD once, reset the inverter and then turn the run signal On again to resume operation. |
2 | Operate after wait time | The inverter starts when the power is turned ON, the low voltage level (LU level) is exceeded and the wait time is passed. (The wait time is set with parameter No. 52) |
3 | "OP" stop | The inverter OP trips when the power is turned ON and the low voltage level (LU level) is exceeded. Turn the run signal On again to resume operation. * When this data is set, the same operation as data setting value "1" will occur when the run signal is input after the power is turned ON, however , the wait time will be waited for during normal starting. |