Functional Descriptions (By Parameter No.) |
OUTPUT TERMINAL FUNCTION SELECT(Parameter No.23) |
Data setting value | Function | Conditions for open collector output to turn ON |
0 | Run signal | ON when run signal is on or during inverter output |
1 | Arrival signal | On when the commanded frequency is within the set frequency +_2Hz |
2 | Overload prealarm | On when the output current is 140% of the rated current of higher or when the electronic thermal level is reached |
3 | Frequency detection signal | On when the commanded frequency exceeds the detected frequency (set in parameter No. 25) |
4 | Reverse run signal | On when the inverter is running in reverse |