Functional Descriptions (By Parameter No.)

OUTPUT TERMINAL FUNCTION SELECT(Parameter No.23)
Data setting value Function Conditions for open collector output to turn ON
0 Run signal ON when run signal is on or during inverter output
1 Arrival signal On when the commanded frequency is within the set frequency +_2Hz
2 Overload prealarm On when the output current is 140% of the rated current of higher or when the electronic thermal level is reached
3 Frequency detection signal On when the commanded frequency exceeds the detected frequency (set in parameter No. 25)
4 Reverse run signal On when the inverter is running in reverse